4.3 Module status information (Register 3x+8)
The information provided in this register is generic information about this
module. Bits 1-8 and 10 provide error status information. Bits 11-16 indicate
what information is present in the current inputs registers.
1 2 3 4 5 6 7 8 9 10 111213141516
Group Select
Data Input Mode Selected
Configuration Error
Reserve
Out of range Channel 1-4
Out of range Channel 5-8
Out of range Channel 9-12
Out of range Channel 13-16
Out of range Channel 17-20
Out of range Channel 21-24
Out of range Channel 25-28
Out of range Channel 29-32
3x+8 Out of Range Error: Bits 1-8
These eight bits indicate that an over or under range condition or an alarm
condition exists on at least one channel within the group. Bits 1-8 correspond
to eight groups of four channels each. When an Out of Range Flag is set,
the Channel Status mode (see Section 4.3) can be enabled to report which
channel is out of range.
Note: An over range error indicates that a channel input is a value greater than or equal to the
maximum for the range selected for that channel group. An under range error indicates
that a channel input is a value less than or equal to the minimum for the selected range.
3x+8 Reserved: Bit 9
Bit 9 should always respond with a 0.