Selecting the Calibration Rate: Register 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x8205
NU NU NU NU NU
Calibration Rate
Calibration Rate:
Bit 7 Bit 8 Description:
0 0 Once at power up only.
0 1 Once every 60 seconds.
*1 0 Once every 10 minutes.
1 1 Once every 30 minutes.
* The default calibrate rate is once every 10 minutes.
Once you have established the correct bit pattern for each of these three
registers, you can convert each to a four digit Hex value that is used in the
parameters screen. A Hex conversion table follows:
0000=0
0001=1
0010=2
0011=3
0100=4
0101=5
0110=6
0111=7
1000=8
1001=9
1010=A
1011=B
1100=C
1101=D
1110=E
1111=F
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 ACI 052 00sc