Selecting Filter Frequencies: Register 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2000 (0x2924 for 140 ACI 050sc)
NU NU Filter Frequency Group 1
Selecting Filter Frequencies: Register 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2A92
NU NU NU NU Filter Frequency Group 2
Filter Frequency Group 3
Filter Frequency Group 4
Range Selection Bit Pattern:
Filter for Group 1 Filter for Group 2
Reg 1 Bit 3 Bit 4 Description Reg 2 Bit 15 Bit 16 Description
0 0 10 Hz 0 0 10 Hz
0 1 50 Hz 0 1 50 Hz
*1 0 60 Hz *1 0 60 Hz
1 1 1000 Hz 1 1 1000 Hz
Filter for Group 3 Filter for Group 4
Reg 2 Bit 12 Bit 13 Description Reg 2 Bit 9 Bit 10 Description
0 0 10 Hz 0 0 10 Hz
0 1 50 Hz 0 1 50 Hz
*1 0 60 Hz *1 0 60 Hz
1 1 1000 Hz 1 1 1000 Hz
* The default filter frequency is 60 Hz.