68 Compact IO
Universal Input Module
Environmental
Conditions
Mechanical Standard Class/Limit
Vibration/Shock Unpack
Shock & Vibration (op) IEC 68-2-6 FC
ICCG-ES #001 A.
Class III
Free Fall Unpackaged (non-op) IEC 68-2-32#1
Shock Unpackaged (op) IEC 68-2-27Ea
ICCG-ES #002 A.
Class III, Cat. I
Packaging Tests NSTA
Temperature 0 to 60 Degree C
Temp Cycle (op) IEC 68-2-14Nb
ICCG-ES #006 C.
0 to +60 2 cycles .5hr/cycle
Thermal mapping of hot comp Done at 60 deg C, full load
Storage Temperature -40 to 85 Degree C
High temp (non-op) IEC 68-2-2Bb
ICCG-ES #006 C.
+85 for 16hrs
Low temp (non-op) IEC 68-2-2Ab
ICCG-ES #006 C.
-40 for 16hrs
Temp Cycle (non-op) IEC 68-2-14Na
ICCG-ES #006 C.
-40 to +85 2 cycles .5hr/cycle
Humidity/Pressure 5 to 95% RH (non cond.)
(non op) IEC 68-2-30 Db 5 deg 95% 24hrs
( op) IEC 68-2-30 Db
ICCG-ES #008 B.
5 deg 95% 24hrs
Regulatory
Compliance
UL 508
CSA (Class 1, Div 2, Group A,B,C,D)
CE compliance to EN 61010-1 and EN 61131-2
EN60079-0, EN60079-15 ATEX
ANSI/ISA 12.12.01
ATEX Special Conditions for Safe Use
Provisions shall be made to prevent the rated voltage being exceeded
by the transient disturbances of more than 40%.
The system shall be mounted in an ATEX certified enclosure with a
minimum ingress protection rating of at least IP54 as defined in
IEC60529 or EN60529 and used in an environment of not more than
pollution degree 2.