Chapter 8: Ladder Program Examples 101
Rung 3 - This is an optional example rung indicating how to send on-the-
fly configuration data to the module. This is useful if you would like to
change channel alarm or scaling tags without causing interruption in
channel updates. Changing other tags will cause a 2.5 second delay in
channel updates but the connection will not be interrupted.
Continued on next page...
You may use either the SetAttributeAll or the Module Reconfigure
message.