Spectrum-controls 1746sc-NI8u Manuel d'utilisateur Page 78

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 130
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 77
66 SLC 500
Universal Analog Input Module
Channel Error (Bit 15)
The module sets this fault bit when it detects any of the following:
Configuration erorrs:
- configuration bits Data Format definition, invalid Input Types for
channels 0 through 3: 10010 - 11101
- configuration bits Data Format definition of Engineering Units x 1 for
Input Types of ±500mV, 0-5V, 1-5V, 0-10V, ±10V, 0-20mA
- configuration bits where Open Circuit is enabled with Input types of 0-
5V, 1-5V, 0-10V, ±10V, or 0-20mA
- invalid data acquisition of an input channel
- the filter frequency selected for the valid channel currently fails
autocalibration range checks
Module Status LED (Green)
The module-status LED indicates when the module detects a
nonrecoverable fault at power up or during operation. For this type of
fault, the module:
no longer communicates with the SLC processor
disables all channels
clears all data and status words
A module failure is non-recoverable and requires the assistance of your
local distributor or Spectrum Controls.
Interpreting I/O Error
Codes
I/O error codes appear in word S:6 of the SLC processor status file. The
first two digits of the error code identify the slot (in hexadecimal) with the
error. The last two digits identify the I/O error code (in hexadecimal).
The error codes that apply to your module include (in hexadecimal):
50–5E
71 (watchdog error)
90–94
For a description of the error codes, refer to the Allen-Bradley Advanced
Programming Software (APS) Reference Manual, Allen-Bradley
publication 1746-6.11.
Vue de la page 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 129 130

Commentaires sur ces manuels

Pas de commentaire