16-Channel Universal Analog Input Module
21
Bit Selection Pattern: Input Data Format for Group 1, 2, 3, 4 - Zoom Register 2,4,6,8
Bit 11 Bit 12 Description
0 0 16 bit unsigned integer
0 1 DVM (Default)
1 0 12 bit unsigned integer
1 1 15 bit signed integer
Bit Selection Pattern: Fault Detect for Group 1, 2, 3, 4 - Zoom Register 2,4,6,8
Bit 9 Bit 10 Description
0 0 Disabled
0 1 Max. on Fault (Default)
1 0 Mi.n. on Fault
1 1 0 on Fault
Bit Selection Pattern: Temperature Units for Group 1, 2, 3, 4 - Zoom Register 2,4,6,8
Bit 8 Description
0 Degrees Celcius (Default)
1 Degrees Farenheight
Once you have established the correct bit pattern for each of these three registers, you can convert each to a
four digit Hex value that is used in the parameters screen. A Hex conversion table follows:
0000=0
0001=1
0010=2
0011=3
0100=4
0101=5
0110=6
0111=7
1000=8
1001=9
1010=A
1011=B
1100=C
1101=D
1110=E
1111=F